The documentation set for this product strives to use bias-free language. For the purposes of this documentation set, bias-free is defined as language that does not imply discrimination based on age, disability, gender, racial identity, ethnic identity, sexual orientation, socioeconomic status, and intersectionality. Exceptions may be present in the documentation due to language that is hardcoded in the user interfaces of the product software, language used based on RFP documentation, or language that is used by a referenced third-party product. Learn more about how Cisco is using Inclusive Language.
Switch |
Width |
Depth |
Height |
---|---|---|---|
Cisco Nexus 9364C-H1 |
17.41 inches (44.23 cm) |
22.27 inches (56.58 cm) |
3.4 inches (8.6 cm) (2 RU) |
Component |
Weight per Unit |
Quantity |
---|---|---|
Cisco Nexus 9364C-H1 Chassis (N9K-C9364C-H1) |
44 lb (20 kg) |
1 |
Fan Module – Port-side exhaust (blue) (NXASFAN-160CFM-2PE) – Port-side intake (red) (NXA-FAN-160CFM-2PI) |
— 1.3 lb (0.59 kg) 1.3 lb (0.59 kg) |
2 |
Power Supply module – 1400-W AC port-side exhaust (blue) (NXA-PAC-1400W-PE) – 1400-W AC port-side intake (red) (NXA-PAC-1400W-PI) – 2000-W HVAC/HVDC port intake (red) (NXA-PHV-2KW-PI) – 2000-W DC port-side exhaust (blue) (NXA-PDC-2KW-PE) – 2000-W DC port-side intake (red) (NXA-PDC-2KW-PI) |
— 2.64 lb (1.2 kg) 2.64 lb (1.2 kg) 2.42 lb (1.1 kg) 2.42 lb (1.1 kg) 2.42 lb (1.1 kg) |
4 (3 for operations and 1 for redundancy) |
To see the transceiver specifications and installation information, see https://www.cisco.com/c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
The following table lists the typical amount of power that the switch consumes. It also lists the maximum amount of power that you must provision for the switch and power supply for peak conditions.
Note |
Some power supplies have capabilities that are greater than the maximum power requirements for a switch. To determine the power consumption characteristics for the switch, use the typical and maximum requirements that are listed in the following table. |
Switch | Typical Power Consumption (AC or DC) | Maximum Power Consumption (AC or DC) | Heat Dissipation Requirement |
---|---|---|---|
Cisco Nexus 9364C-H1 |
605 W |
1100 W |
4248.116 BTUs per hour |
Power specifications include the specifications for each type of power supply module.
Property | Specification |
---|---|
Power |
1400 W |
Input Voltage Range |
90 VAC to 140 VAC 180 VAC to 264 VAC |
Output Power |
1,000W/36W 1,450W/36W |
Output 1 |
Main: 12V/84A Main: 12V/121A |
Output 2 |
Standby: 12V/3A |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
These specifications apply to the NXA-PAC-2KW power supplies.
Property | Specification |
---|---|
Power |
2000 W |
Input Voltage |
200-240 VAC, 12A, 50/60 Hz or -48 to -60Vdc, 55A or 200-277 VAC, 12A, 50/60Hz or 240V-380VDC, 12A |
Frequency |
50 to 60 Hz |
Efficiency |
90% or greater (20 to 100% load) |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
These specifications apply to the NXA-PHV-2KW power supplies.
Property | Specification |
---|---|
Power |
2000 W |
Input Voltage |
180 to 305 VAC or 192 to 400 VDC |
Frequency |
50 to 60 Hz |
Efficiency |
90% or greater (20 to 100% load) |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
These specifications apply to the NXA-PDC-2KW power supplies.
Property | Specification |
---|---|
Power |
2000 W |
Input Voltage |
Minimum to Maximum: -40 to -70 VDC Nominal: -48 to -60 VDC |
Frequency |
- |
Efficiency |
90% or greater (20 to 100% load) |
Redundancy Modes |
Combined, n+1, and n+n |
RoHS Compliance |
Yes |
Hot Swappable |
Yes |
The following sections specify the power cables that you can order and use with this switch.
Power Type | Power Cord Part Number | Cord Set Description |
---|---|---|
CAB-C13-C14-2M |
Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m) |
|
CAB-C13-CBN |
Cabinet jumper power cord, 250 VAC, 10 A, C14-C13 connectors, 2.3 feet (0.7 m) |
|
Argentina |
CAB-250V-10A-AR |
250 V, 10 A, 8.2 feet (2.5 m) |
Australia |
CAB-9K10A-AU |
250 VAC, 10 A, 3112 plug, 8.2 feet (2.5 m) |
Brazil |
CAB-250V-10A-BR |
250 V, 10 A, 6.9 feet (2.1 m) |
European Union |
CAB-9K10A-EU |
250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m) |
India |
CAB-IND-10A |
10 A, 8.2 feet (2.5 m) |
India |
CAB-C13-C14-2M-IN |
Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m) |
India |
CAB-C13-C14-3M-IN |
Power Cord Jumper, C13-C14 Connectors, 9.8 feet (3.0 m) |
Israel |
CAB-250V-10A-IS |
250 V, 10 A, 8.2 feet (2.5 m) |
Italy |
CAB-9K10A-IT |
250 VAC, 10 A, CEI 23-16/VII plug, 8.2 feet (2.5 m) |
Japan |
CAB-C13-C14-2M-JP |
Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m) |
North America |
CAB-9K12A-NA |
125 VAC, 13 A, NEMA 5-15 plug, 8.2 feet (2.5 m) |
North America |
CAB-AC-L620-C13 |
NEMA L6-20-C13, 6.6 feet (2.0 m) |
North America |
CAB-N5K6A-NA |
200/240V, 6A, 8.2 feet (2.5 m) |
Peoples Republic of China |
CAB-250V-10A-CN |
250 V, 10 A, 8.2 feet (2.5 m) |
South Africa |
CAB-250V-10A-ID |
250 V, 10 A, 8.2 feet (2.5 m) |
Switzerland |
CAB-9K10A-SW |
250 VAC, 10 A, MP232 plug, 8.2 feet (2.5 m) |
United Kingdom |
CAB-9K10A-UK |
250 VAC, 10 A, BS1363 plug (13 A fuse), 8.2 (2.5 m) |
All except Argentina, Brazil, and Japan |
NO-POWER-CORD |
No power cord included with switch |
Cable |
Description |
Illustration |
---|---|---|
CAB-TA-NA |
North America AC Type A Power Cable |
|
CAB-TA-UK |
United Kingdom AC Type A Power Cable |
|
CAB-TA-250V-JP |
Japan 250V AC Type A Power Cable |
|
CAB-TA-EU |
Europe AC Type A Power Cable |
|
CAB-C15-CBN |
Cabinet Jumper Power Cord, 250 VAC 13A, C14-C15 Connectors |
|
CAB-ACBZ-12A |
AC Power Cord (Brazil) 12A/125V BR-3-20 plug up to 12A |
|
CAB-TA-IN |
India AC Type A Power Cable |
|
CAB-TA-IS |
Israel AC Type A Power Cable |
Part Number |
Cord Set Description |
Photo |
---|---|---|
CAB-HVAC-SD-0.6M |
HVAC 2-foot (0.6 m) cable with Saf-D-Grid and SD connectors 277V AC |
|
CAB-HVAC-C14-2M |
HVAC 6.6-foot (2.0 m) cable with Saf-D-Grid and C14 (use for up to 240 V) connector 250V AC |
|
CAB-HVAC-RT-0.6M |
HVAC 2-foot (0.6 m) cable with Saf-D-Grid and RT connector 277V AC |
|
CAB-HVDC-3T-2M |
HVDC 6.6-foot (2.0 m) cable with Saf-D-Grid and three terminal connectors 300V AC / 400V DC (+200/-200 V DC) |
|
NO-POWER-CORD |
All except Argentina, Brazil, and Japan No power cord included with switch |
Not applicable |
1 |
Connect this end to the power supply unit. |
The following table lists the regulatory standards compliance for the switch.
Specification |
Description |
---|---|
Regulatory compliance |
Products should comply with CE Markings according to directives 2004/108/EC and 2006/95/EC. |
Safety |
|
EMC: Emissions |
|
EMC: Immunity |
|
RoHS |
The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. |